Mobile:86-18680475290
Tel:86-577-61670617
Fax:86-577-62051190
Web:www.lbaji.com
- product name : LBM10LE-250/430 Molded Case Circuit Breaker
- product brand : LBAJI
- Place of Origin : CHINA
- E-mail : sales@labji.com
- Online Contact :
Application
LBM10 series molded case circuit breaker(hereinafter referred to as circuit breakder) is suitable for distributing network of AC 50Hz(or 60Hz). RATED CURRENT 15~600A, rated insulation voltage 690V and rated working voltage 400V or below. It can be usedto distribute electric energy and protect the circuit and electric equipment against overload, short circuit and under voltage,under normal condition,the circuit breaker also can be used to switch the circuit infrequently. Circuit breakers of framesize 250A and below also can be used to protect motor or infrequently start motor.
The products are in conformity with GB 14048.2 GB 14048.4, IEC 60947-2 and IEC 60947-4 .
Main technical data
1 . Main technical parameters of circuit breaker
Type |
(A) Rated frame current |
ln(A) Rated current |
(W)Power loss |
Rated Service short-circuit breaking capability | Rated Ultimate short-circuit breaking capability |
mm Flash over distance | ||
lcs kA | CosΦ | lcs kA | CosΦ | |||||
LBM10-100 |
100 |
15,20,25,30 40,50,60,80, 100 |
25 |
5 |
0.5 |
10 |
0 .3 |
200 |
LBM10-250 |
250 |
100,120( 125) ,140(150),170,200(225) ,250 |
55 |
10 |
0.3 |
20 |
0.25 |
200 |
LBM10-600 |
600 |
200, 250,300,350, 400 ,500' 600 |
130 |
12 .5 |
0.3 |
25 |
0.25 |
250 |
Note: The rated current level in the bracket is regarded as special specification,if necessary,the manufacturer can make special design for you.
2 . Main technical parameters of control circuit
Sort |
V Rated Working voltage | |||
AC 50Hz |
DC | |||
Release |
shunt release |
Us |
230 ,400 |
24 , 110 , 220 |
Under voltage release |
Ue |
230 , 400 |
||
ectric mechanism |
Us | 230 , 400 |
3 . nain technical parameters of auxiliary contact
lth(A) Conventional thermal curent |
Ui(V) Rated insulation Voltage |
le Rated working current |
Rated frame current | |
AC400V |
D C220V | |||
3 |
400 |
0.26 | 0.15 | 225A及以下 |
0 .4 |
0 .2 |
400A及以下 |
4. Setting value of short-circuit protection current
Type |
Test current for distribution protection |
Test current for Motor protection | Accuracy of setting value | Conventional time |
lntiap state |
RMM10-100, 250 |
10ln |
12In | ±20% | <0.2 Trip |
Cold state |
RMM10- 600 |
- |
5. Inverse time lag breaking characteristice of circuit breaker for distribution protection
Name of test current |
Current setting multiple |
T Conventional time |
Intiap state |
Ambient temperature | ||
1.01ln≤100 A | 63A |
225A | ||||
Conventional non-tripping current |
1.051n |
≤1h |
≥2h |
Cold state |
+ 30℃ | |
Conventional tripping current |
1.301n |
< 1h |
<2h |
Hot state | ||
Returnable time |
3.0ln |
Returnable time |
Cold state | |||
5s |
8s |
12s |
6.lnversl time lag characteristics of circuit breaker for motor protection
Name of test current |
Current setting multiple |
T Conventional time | lntiap state |
Ambient temperature | |
1.01In≤100A | 100A<In≤225A | ||||
Conventional non·ripping current | 1.01In | ≥2h | Cold state | ||
Conventional tripping current | 1.2In | <2h | Hot state | + 40℃ | |
1.5In | ≥2min | ≤4min | Hot state | ||
Current of returning characterstic | 7.2In | 2s |
4s |
Cold state |
OutIine & installation size
Type | Outline Size | Connection size | ||||||||||
L | W | H | H1 | H2 | a | b | Φd | a1 | b1 | Φd1 | H3 | |
RMM10-100 | 153 | 108 | 104 | 83 | 23.5 | 35 | 135 | 5 | 70 | 131 | 6 | 53 |
RMM10-250 | 276 | 155 | 142 | 105 | 34 | 51 | 240 | 10 | 102 | 238 | 10 | 54 |
RMM10-600 | 396 | 210 | 147 | 109 | 39 | 70 | 361 | 11 | 140 | 325 | 12 | 45 |